Instructions for interfacing the Turner Designs C6 with a NexSens iSIC data logger:

IMPORTANT: Review the manufacturer’s manual for the sensor to ensure that the sensor is properly configured for integration with a third party data logger prior to connecting the device to the iSIC. 

1. Route cables and wires through one of the gland fittings installed on the iSIC enclosure.

2. Unplug the green terminal strip from the iSIC before inserting sensor wiring. The left terminal strip is designated for digital inputs (RS-485, RS-232, SDI-12, etc.) ; the right for analog inputs (mV, 4-20 mA, etc.).

3. Connect the sensor wires to the terminal strip as shown in the diagram below.

IMPORTANT: Verify that no wires are loose or clamped on the insulation as this will cause intermittent or failed communication. Seal and caulk the gland fitting to prevent moisture intrusion and maintain the NEMA4X rating of the iSIC enclosure.

 

Turner Designs C6

Figure 1: Wiring a Turner Designs C6 into an iSIC Data Logger.

Notes:

  • The C6 should be wired with switched power because it draws a significant amount of current while running idle.
  • P2.Rx and P2.Tx must be used in place of P1.Rx and P1.Tx when wiring two sensors to the iSIC terminal strip.
Turner C6 Wiring Table

Figure 2: Table for wiring a Turner Designs C6 to an iSIC Data Logger.

 

4. Add the Device through the iChart Setup Device Wizard, and refer to the iChart Knowledge Base for additional information and troubleshooting.

 

REV: 13G25

Leave a Reply

Your email address will not be published. Required fields are marked *