NexSens MCIL-8-MP Port Pinout


NexSens X2-SDLMC, X2-CBMC, and X3-SUB data loggers incorporate MCIL-8-MP plugs for connection of sensor cables with MCIL-8-FS plug connectors. The pinout for the sensor ports is as follows:

Figure 1: MCIL-8-MP pinout

Note: All splitter extensions contain the same pinout and signal configuration; however, only one 232 sensor can be connected to each splitter/port. The arrow on the 2-way splitter and the end port on the 4-way splitter indicates on which port the 232 sensor may be connected.

MCIL-8-MP Sensor Port Pin#Signal
1RS232-Tx*
2GND
3RS232-Rx*
4
5Power (12VDC)
6SDI-12
7RS-485B
8RS-485A